Plan Review Notes
Plan Review Notes For Permit 23060469
Permit Number 23060469
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-06-16 10:13:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE EXHAUST DUCT PASSING
 THROUGH A RATED FIRE WALL AND ALSO SHOWING A DUCT AT
 TWO LOCATION OF THE SMALLER DUCT.
  
 PER NFPA 96
  
 7.1 GENERAL.
  
 7.1.1 DUCTS SHALL NOT PASS THROUGH FIRE WALLS.
  
 7.1.2* ALL DUCTS SHALL LEAD DIRECTLY TO THE EXTERIOR OF
 THE BUILDING, SO AS NOT TO UNDULY INCREASE ANY FIRE
 HAZARD.
  
 7.1.3 DUCT SYSTEMS SHALL NOT BE INTERCONNECTED WITH ANY
 OTHER BUILDING VENTILATION OR EXHAUST SYSTEM.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE A DETAILED
 NARRATIVE WITH CODE REFERENCES AND IF APPLICABLE
 ADDITIONAL DRAWINGS INDICATING COMPLIANCE.
  
  
  
 2) THERE ARE INDCATIONS OF AN UPWARD SLOPE OF THE
 EHAUST DUCT WITH A 1/4 & 12 SLOPE; HOWEVER, THERE IS NO
 INDICATION OF WHAT THE 1/4 STANDS FOR NOR AN OVERALL
 LENGTH DIMENSION OF THE DUCT.
  
 PER NFPA 96
  
 7.1.4 ALL DUCTS SHALL BE INSTALLED WITH A MINIMUM 2
 PERCENT
 SLOPE ON HORIZONTAL RUNS UP TO 22.86M(75 FT) AND A
 MINIMUM
 8 PERCENT SLOPE ON HORIZONTAL RUNS GREATER THAN 22.86 M
 (75 FT).
  
 PLEASE REVIEW AND CORRECT, INCLUDING THE % OF SLOPE, OR
 PROVIDE A DETAILED NARRATIVE WITH CODE REFERENCES AND
 IF APPLICABLE ADDITIONAL DRAWINGS INDICATING
 COMPLIANCE.
  
  
  
 3) THERE ARE NO INDICATIONS OF A DRAIN. THERE ARE
 INDIACTIONS OF CLEAN OUTS BUT NO DRAIN.
  
 PER NFPA 96
  
 7.1.4.3* DRAINS SHALL BE PROVIDED AT LOW POINTS IN
 HORIZONTAL
 DUCTS.
  
 7.1.4.3.1 WHERE PROVIDED, DRAINS SHALL BE CONTINUOUSLY
 WELDED TO THE EXHAUST DUCT OR LISTED GREASE DUCT
 DRAINS, IN
 ACCORDANCE WITH THE TERMS OF THE LISTING AND THE
 MANUFACTURER???S
 INSTALLATION MANUAL.
  
 PLEASE REVIEW AND CORRECT. PROVIDE THE SPECIFIC DRAIN
 LOCATION(S).
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  