| Plan Review Notes For Permit 23060447 |
| Permit Number |
23060447 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-06-28 18:42:50 | PLAN REVIEWER: ED ROSEBERRY PX2909 | | | EMAIL: [email protected] | | | PH: 772-359-3502 | | | ***PRIMARY CONTACT IS EMAIL*** | | | | | | 1. NOTE ON YOUR FLOOR PLAN REGARDING BACKING ROD AND | | | SEALANT IS IN DIRECT CONFLICT WITH THE SUBMITTED | | | PRODUCT APPROVAL, SEVENTH SECTION ON SHEET 1 OF 12, | | | BEGINNING WITH THE STATEMENT, " THIS PRODUCT APPROVAL | | | IS GENERIC...". | | | PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO THE | | | PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR FBC | | | B 1405.4. AN ENGINEERED FLASHING DETAIL WILL ALSO | | | COMPLY WITH THIS CODE REQUIREMENT. ***NOTE*** THIS IS | | | NOT USUALLY INCLUDED IN FBC/NOA. COMPLIANCE MUST BE | | | SHOWN SEPARATELY. |
|