| Plan Review Notes For Permit 23060409 |
| Permit Number |
23060409 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-06-16 16:16:59 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 23060409 | | | 6/16/23 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A-1.01A: PLEASE CLARIFY THE SCOPE OF GAS WORK- | | | SEC. 107.2.1 WPB. THERE IS A NOTE ON THE PLAN | | | REFERENCING A GAS RISER WHICH IS NOT SHOWN ON THE | | | PLANS. PLEASE PROVIDE THE RISER- SEC. 107.3.5.1.5 WPB. | | | | | | 2) A-1.01A: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE | | | NEW RANGE- SEC. 304.1 FBC FG. IF USING THE STANDARD | | | METHOD OF INDOOR AIR PER SEC. 304.5.1 THE MINIMUM | | | REQUIRED VOLUME IS 50 CU. FT. PER 1000 BTUH. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|