Plan Review Notes
Plan Review Notes For Permit 23060409
Permit Number 23060409
Review Stop G
Sequence Number 1
Notes
Date Text
2023-06-16 16:16:591ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23060409
 6/16/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-1.01A: PLEASE CLARIFY THE SCOPE OF GAS WORK-
 SEC. 107.2.1 WPB. THERE IS A NOTE ON THE PLAN
 REFERENCING A GAS RISER WHICH IS NOT SHOWN ON THE
 PLANS. PLEASE PROVIDE THE RISER- SEC. 107.3.5.1.5 WPB.
  
 2) A-1.01A: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 NEW RANGE- SEC. 304.1 FBC FG. IF USING THE STANDARD
 METHOD OF INDOOR AIR PER SEC. 304.5.1 THE MINIMUM
 REQUIRED VOLUME IS 50 CU. FT. PER 1000 BTUH.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  