2023-06-13 10:26:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF INSTALLING NEW CARPET IS
 SOME ROOMS, HOWEVER, THERE IS NO INDICATION OF THE
 REPLACEMENT CARPET PRODUCT NAME NOR A SPEC SHEET.
  
 THERE ARE NO DETAILS ON THE FLOOR FINNISH PLAN.
  
 CARPET IS MANUFACTURED AROUND THE WORLD AND NOT ALL ARE
 TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
  
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE CARPET
 PRODUCT NAME AND THE PRODUCT SPEC SHEETS INDICATING THE
 FIRE BEHAVIOR RATING.
  
  
  
 2) THERE ARE INDICATIONS OF WALLS BEING REMOVED AND NEW
 WALL CONSTRUCTION.
  
 FIRE PROVISO:
  
 ANY REMOVAL OR CONSTRUCTION OF WALLS/CEILINGS REQUIRES
 AND EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS FOR CODE COMPLIANT COVERAGE
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PLEASE ENSURE APPLICABLE PROTECTION AND PROVIDE A NOTE
 OF ACKNOWLEDGMENT ON THE FLOOR PLAN.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  