| 2023-07-27 11:11:13 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL1654-R31 HAS BEEN REVISED TO FL1654-R32. |
| | PLEASE PROVIDE THE FOLLOWING: COVER PAGE, EVALUATION |
| | REPORT PAGES 1-5 AND INSTALLATION INSTRUCTIONS PAGE FOR |
| | SYSTEM USED HIGHLIGHTED/CIRCLED. ALL APPLICABLE DETAILS |
| | AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| | PRODUCT APPROVAL DRAWINGS. |
| | 2. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY |
| | CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER TO UPDATE PRODUCT |
| | APPROVAL TO THE CURRENT APPROVED VERSION |
| | FL1654-R32; INCLUDE UPDATED SYSTEM/PAGE NUMBER TO BE |
| | USED (IF APPLICABLE). |
| | 3. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S), MEAN |
| | ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE |
| | DRAINAGE. SECOND REQUEST. |
| | 4. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE |
| | IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO |
| | WALL CONNECTIONS WILL BE IMPROVED. SECOND REQUEST. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |