Plan Review Notes
Plan Review Notes For Permit 23060323
Permit Number 23060323
Review Stop B
Sequence Number 1
Notes
Date Text
2023-06-29 13:19:22JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. SUBMITTED PRODUCT APPROVAL FL1654-R30 HAS BEEN
 REVISED TO FL1654-R32. PLEASE PROVIDE THE FOLLOWING:
 INCLUDE COVER PAGE, EVALUATION REPORT PAGES 1-5 AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. FL1654-R30
 SYSTEM NO. W-141 DO NOT MEET THE MINIMUM ZONE 3 DESIGN
 PRESSURE REQUIREMENT OF -131.42 FOR EXPOSURE CATEGORY D
 AREAS. PROVIDE SYSTEM THAT MEETS OR EXCEEDS ALL DESIGN
 PRESSURE REQUIREMENTS FOR EXPOSURE CATEGORY D/PROVIDE
 SIGNED AND SEALED ENGINEERED NAILING CALCULATIONS WITH
 AN APPROVED SYSTEM.
 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S), MEAN
 ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE
 DRAINAGE.
 3. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE
 IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO
 WALL CONNECTIONS WILL BE IMPROVED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  