| Plan Review Notes For Permit 23060318 |
| Permit Number |
23060318 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-07-08 22:06:38 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | COMMENTS FROM PREVIOUS REVIEW, NOT ADDRESSED: | | | | | | 1. FBC B 1609 SUBMIT PRODUCT APPROVALS FOR ALL PRPOSED | | | COMPONENTS AND CLADDING. | | | | | | 2. FBC 107 REVISE FLOOR PLAN TO SHOW ALL LOCATION OF | | | PROPOSED INSTALLATIONS, SIZES, TYPE OF WINDOW/DOOR. | | | | | | 3. FBC 107, FBC B CH 10, ON THE DOOR PRODUCT APPROVAL | | | INDICATE THE THRESHOLD PROPOSED, WHETHER OR NOT PANIC | | | DEVICE IS PROPOSED. | | | | | | 2ND REVIEW: | | | | | | 4. RESPONSE LETTER STATES THAT HARDWARE IS NOT IN THEIR | | | CONTRACT. THIS IS A COMMERCIAL BUILDING. ALL | | | MODIFICATIONS TO THE COMPONENTS AND CLADDING, MEANS OF | | | EGRESS, ARE TO BE INCLUDED IN THIS PERMIT. | | | | | | | | | |
|