| Plan Review Notes For Permit 23060318 |
| Permit Number |
23060318 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-06-23 13:29:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS OF MARKED X'S ON THE OUTSIDE | | | LINES OF THE ATTACHED DRAWING. | | | | | | THERE ARE NO INDICATIONS OF WHAT THESE MARKED X'S | | | REPRESENT, INCLUIDNG TYPE AND SIZES. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TYPE OF | | | OPENINGS AND THE REPLACEMENT SIZES. | | | | | | | | | 2) THERE APPEARS TO BE 2 DOORS THAT MAY BE INCLUDING IN | | | THE MARKED X'S, HOWEVER, THERE IS NO DOOR SCHEDULE THAT | | | INCLUDES, SIZE AND EXIT HARDWARE/LOCKS AND LATCHES THAT | | | CONFOMR TO NFPA 101 CH 7, MEANS OF EGRESS. | | | | | | PLEASE REVIEW AND PROVIDE DOOR & HARDWARE DETAILS. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|