Plan Review Notes
Plan Review Notes For Permit 23060315
Permit Number 23060315
Review Stop B
Sequence Number 1
Notes
Date Text
2023-06-23 17:04:54R4501.17.1.8 ACCESS GATES, WHEN PROVIDED, SHALL BE
 SELF-CLOSING AND SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTIONS R4501.17.1.1 THROUGH R4501.17.1.7 AND
 SHALL BE EQUIPPED WITH A SELF-LATCHING LOCKING DEVICE
 LOCATED ON THE POOL SIDE OF THE GATE. WHERE THE
 DEVICE RELEASE IS LOCATED NO LESS THAN 54 INCHES
 (1372 MM) FROM THE BOTTOM OF THE GATE, THE DEVICE
 RELEASE MECHANISM MAY BE LOCATED ON EITHER SIDE OF
 THE GATE AND SO PLACED THAT IT CANNOT BE REACHED BY A
 YOUNG CHILD OVER THE TOP OR THROUGH ANY OPENING OR
 GAP FROM THE OUTSIDE. GATES THAT PROVIDE ACCESS TO
 THE SWIMMING POOL MUST OPEN OUTWARD AWAY FROM THE
 POOL. THE GATES AND BARRIER SHALL HAVE NO OPENING
 GREATER THAN 1/2 INCH (12.7 MM) WITHIN 18 INCHES (457
 MM) OF THE RELEASE MECHANISM
  
 PLEASE PROVIDE GATE CLOSING MECHANISM INFO AS PER CODE
 CITED ABOVE.
  
  
 FBC 107.2.1
 PROVIDE FENCE POLE FOUNDATIONS SECTIONS AND MAKE SURE
 ALL EASEMENT HAVE BEEN CLEARED
  
 IF ANY QUESTIONS OF CONCERNS YOU MAY CONTAACT ME
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved