Plan Review Notes
Plan Review Notes For Permit 23060302
Permit Number 23060302
Review Stop SIGNATURE
Sequence Number 1
Notes
Date Text
2023-06-27 12:35:071ST SIGNATURES FBC-2020 RES. GAS
 PERMIT- 23060302
 6/27/23
  
 CODES IN EFFECT:
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE TANK ANCHORAGE SUBMITTAL FROM TIE DOWN
 ENGINEERING HAS OUTDATED CODE REFERENCES AND IS NOT
 DIGITALLY SIGNED AND SEALED BY THE ENGINEER OF RECORD-
 SECS. 107.2.1 WPB AND FL. STATUTE 471.025 AND SEC.
 61G15-23.005 FAC. PLEASE NOTE THE TIE DOWN ENGINEERING
 IS GENERIC AND SHALL BE MARKED UP BY THE ENGINEER TO
 SHOW THE PHYSICAL ADDRESS OF THE TANK, THE SIZE OF THE
 TANK, THE NUMBER AND TYPE OF TIE DOWN STRAPS OR CABLES,
 AND THE SOIL CLASSIFICATION AND SIZE OF AUGERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  