| 2023-06-27 12:31:59 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23060302 |
| | 6/27/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | NFPA 58-2014 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SURVEY SHOWS THE TANK WILL BE LOCATED IN THE |
| | DRIVEWAY. PLEASE SHOW THE LOCATION WILL BE A MINIMUM 10 |
| | FT. AWAY FROM THE BUILDING AND THE PROPERTY LINES- SEC. |
| | 6.3.3.2 NFPA 58. |
| | |
| | 2) PROVIDE A TANK PROFILE DETAIL SHOWING THE BURIAL |
| | DEPTH, CLEARANCE FROM GRADE, HOW ACCESS TO THE SHUTOFF |
| | VALVE AND REGULATOR WILL BE PROVIDED, AND HOW THE TANK |
| | AND CONTROLS WILL BE PROTECTED FROM VEHICULAR DAMAGE- |
| | SECS. 6.6.6.1 B, C, & E. |
| | |
| | 3) THE TANK ANCHORAGE SUBMITTAL FROM TIE DOWN |
| | ENGINEERING HAS OUTDATED CODE REFERENCES AND IS NOT |
| | DIGITALLY SIGNED AND SEALED BY THE ENGINEER OF RECORD- |
| | SECS. 107.2.1 WPB AND FL. STATUTE 471.025 AND SEC. |
| | 61G15-23.005 FAC. PLEASE NOTE THE TIE DOWN ENGINEERING |
| | IS GENERIC AND SHALL BE MARKED UP BY THE ENGINEER TO |
| | SHOW THE PHYSICAL ADDRESS OF THE TANK, THE SIZE OF THE |
| | TANK, THE NUMBER AND TYPE OF TIE DOWN STRAPS OR CABLES, |
| | AND THE SOIL CLASSIFICATION AND SIZE OF AUGERS. |
| | |
| | 4) THE ANODE SPEC SHEET IS GENERIC AND SHALL BE MARKED |
| | UP TO SHOW THE PRODUCT NUMBER OF THE ANODE TO BE |
| | INSTALLED. PLEASE PROVIDE INSTALLATION AND TESTING |
| | INSTRUCTIONS OR PLACE A NOTE TO INDICATE THEY WILL BE |
| | ONSITE FOR INSPECTION- SECS. 6.17.1- 6.17.3.3 NFPA 58. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |