| Plan Review Notes For Permit 23060257 |
| Permit Number |
23060257 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2023-07-25 10:17:09 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | | | 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R39 | | | (NON- HVHZ) COVERS MULTIPLE ATTACHMENT LIMITATIONS & | | | INSTALLATION APPROVED ASSEMBLIES. SELECT ATTACHMENT | | | LIMITATION SYSTEM FROM 5.8.3.2 MECHANICALLY-ATTACHED | | | BASE SHEET TABLE 4B ALLOWABLE DESIGN PRESSURES, 2-PLY | | | UNDERLAYMENT SYSTEMS IN TILE ROOF APPLICATIONS PAGES | | | #8-14. SELECT SYSTEM THAT MEETS OR EXCEED THE MINIMUM | | | DESIGN PRESSURE REQUIREMENTS FOR A HIP ROOF; 5:12 ROOF | | | SLOPE; MRH 25 FT. MINIMUM DESIGN PRESSURE REQUIREMENT | | | OF -78 IN AN EXPOSURE CATEGORY C AREA. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|