| Plan Review Notes For Permit 23060254 |
| Permit Number |
23060254 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-06-07 11:07:14 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 23060254 | | | 6/7/23 | | | CODES IN EFFECT: | | | | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED SPEC SHEET FOR THE WATTS BACKFLOW | | | PREVENTERS DOES NOT SHOW THE DEVICES MEET THE | | | REQUIREMENTS OF NSF/ANSI/CAN 61 (0.25% MAX WEIGHTED | | | AVERAGE LEAD CONTENT). SUBMIT SPECS FOR THE LF919 THAT | | | SHOWS COMPLIANCE- WPB UTILITIES CROSS-CONNECTION | | | MANUAL. | | | | | | 605.2.1 LEAD CONTENT OF DRINKING WATER PIPE AND | | | FITTINGS. | | | PIPE, PIPE FITTINGS, JOINTS, VALVES, FAUCETS AND | | | FIXTURE FITTINGS UTILIZED TO SUPPLY WATER FOR DRINKING | | | OR COOKING PURPOSES SHALL COMPLY WITH NSF 372 AND SHALL | | | HAVE A WEIGHTED AVERAGE LEAD CONTENT OF 0.25 PERCENT OR | | | LESS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|