| Plan Review Notes For Permit 23060201 |
| Permit Number |
23060201 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-06-15 08:40:38 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE A PRODUCT APPROVAL FOR THE FLAT DECK | | | - PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = NEED TO | | | CHOOSE A ROOFING SYSTEM IN THE PRODUCT APPROVAL THAT | | | SHOWS THE REQUIRED WIND DESIGN PRESSURE PER FBC R TABLE | | | R301.2(2) - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED | | | IN THE PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE | | | ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR | | | ENGINEER FOR THE ROOF ZONES 1, 2 AND 3 WHICH MAY | | | REQUIRE A HIGHER WIND PRESSURE THEN THE CHOSEN ROOFING | | | SYSTEM - SEE NOTES ON THE PRODUCT APPROVAL. |
|