| 2023-06-26 08:15:02 | |
| | 2ND REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23060173 |
| | 6/26/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET PG-1: BASED ON TABLE G2413.4(1) {402.4(2)} FBC |
| | RES. THE 3/4-INCH STEEL PIPE FROM THE METER TO THE |
| | WATER HEATER SHALL BE INCREASED TO 1-INCH. NO SIZE |
| | INCREASE REQUIRED FROM THE BRANCH PIPES TO THE RANGE |
| | AND DRYER. PLEASE NOTE I WAS UNABLE TO LOCATE AN AO |
| | SMITH MODEL ATHMOSN 120,000 BTU TANKLESS WATER HEATER |
| | OR THE MANUFACTURER'S WEBSITE, AND THE SMALLEST |
| | CAPACITY TANKLESS I COULD LOCATE WAS AN ATI MODEL AT |
| | 140,000 BTUS. PLEASE CORRECT THE PLAN AND RISER |
| | DRAWING. |
| | |
| | 2) PG-1: THE COMBUSTION AIR PLAN IS APPROVED HOWEVER |
| | PLEASE NOTE THAT SECS. G2407.1 EXCEPTION 1 AND G2439.5 |
| | ALLOW FOR AN INTERIOR MAKEUP AIR OPENING TO BE USED FOR |
| | THE DRYER INSTEAD USING THE EXTERIOR OPENING PROPOSED. |
| | THE MINIMUM NET AREA INTERIOR OPENING INTO THE |
| | CONNECTING SPACE REQUIRED IS 100 SQ. INCHES. A 12X12 |
| | LOUVER WILL NET 108 SQ. INCHES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |