| 2023-06-08 12:39:46 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23060172 |
| | 6/8/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE PERMITS FOR THE EXISTING TANKLESS WATER HEATER |
| | (PERMIT- 12050777 & ELECT. SUB-PERMIT 12050778) WERE |
| | ISSUED ON 6/4/2012 BUT EXPIRED PRIOR TO COMPLETION. I |
| | HAVE REVOKED BOTH OF THE PERMITS AND THE WATER HEATER |
| | WILL BE INSPECTED AS NEW UNDER THIS NEW GAS PERMIT. |
| | THERE IS ALSO NO RECORD OF A GAS PERMIT FOR THE RANGE |
| | THEREFORE IT SHALL ALSO BE INSPECTED AS NEW UNDER THIS |
| | PERMIT. PLEASE PROVIDE THE FOLLOWING CORRECTIONS TO THE |
| | PLANS. |
| | |
| | A) GAS RISER: THE 1-INCH GALVANIZED PIPE TO THE NEW |
| | POOL HEATER SHALL BE INCREASED TO 1-1/4-INCH PER TABLE |
| | G2413.4(1) FBC RES. & [402.4(2)] FBC FUEL GAS. |
| | |
| | B) PROVIDE A BASIC SITE OR FLOOR PLAN DRAWING SHOWING |
| | THE LOCATIONS OF THE GAS-FIRED APPLIANCES. INCLUDE THE |
| | CLEARANCE DISTANCE MEASUREMENTS FROM THE WATER HEATER |
| | AND POOL HEATER EXHAUST OUTLETS TO NEARBY OPERABLE |
| | WINDOWS AND DOORS- REFER TO SEC. G2427.8 FBC RES. |
| | |
| | C) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE RANGE- |
| | SEC. G2407.1 FBC RES. PLEASE NOTE IF USING THE STANDARD |
| | METHOD OF INDOOR COMBUSTION AIR, THE MINIMUM REQUIRED |
| | VOLUME SHALL BE 50 CU. FT. PER 1,000 BTUH. |
| | |
| | 2) PROVIDE ELECTRICAL AND PLUMBING SUB-PERMIT |
| | APPLICATIONS FOR INSTALLATION OF THE WATER HEATER- SEC. |
| | 105.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |