| Plan Review Notes For Permit 23060156 |
| Permit Number |
23060156 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-06-15 11:47:05 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE THE FLORIDA STATE PRODUCT APPROVAL | | | FRONT PAGES FOR PRODUCT APPROVAL FL38754 | | | | | | 2) PLEASE PROVIDE DETAILS FOR THE ROOF TO WALL | | | CONNECTIONS - FBC EXISTING BUILDING 706.8 WHEN A ROOF | | | COVERING ON AN EXISTING STRUCTURE WITH A SAWN LUMBER, | | | WOOD PLANK OR WOOD STRUCTURAL PANEL ROOF DECK IS | | | REMOVED AND REPLACED ON A BUILDING THAT IS LOCATED IN | | | THE WIND-BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA | | | BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE | | | OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR | | | FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT | | | PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR | | | PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE: | | | | | | (A)ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS | | | REQUIRED BY SECTION 706.8.1. | | | | | | (B)MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION | | | SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN | | | THE COST OF REROOFING. |
|