| 2023-06-07 16:58:44 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23060136 |
| | 6/7/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P3.1 GAS RISER CORRECTIONS: |
| | |
| | A) TOTAL LOAD SHOWN ON RISER IS 1,721,700 BTUH, LOAD IN |
| | SCHEDULE IS 1,138,000. |
| | |
| | B) PIPE TYPE, SIZE, AND LENGTH FROM LOW PRESSURE |
| | REGULATOR TO GENERATOR NOT SHOWN. |
| | |
| | C) LOW PRESSURE REGULATOR BY GWH-2 NOT LABELED. |
| | |
| | D) LOW PRESSURE 1/2--INCH STEEL PIPE FOR A LOAD OF |
| | 330,000 AT TOTAL DEVELOPED LENGTH OF 40 FT. IS |
| | UNDERSIZED PER TABLE 402.4(2). THE MINIMUM SIZE |
| | REQUIRED IS 1-1/4-INCH. |
| | |
| | E) LOW PRESSURE CSST LOAD OF 659,000 BTUH IS INCORRECT. |
| | THE LOAD SHOWN IS 140,000 BTUH. |
| | |
| | F) LOW PRESSURE CSST SIZE OF 25 EHD MUST BE INCREASED |
| | TO EHD 30 PER TABLE 402.4(15) |
| | |
| | G) LOW PRESSURE 1/2--INCH STEEL DROP TO 100,000 BTUH |
| | COOKTOP SHALL BE INCREASED TO 3/4-INCH- TABLE 402.4(2). |
| | |
| | H) PIPE TYPE, SIZE, AND LENGTH FROM LOW PRESSURE |
| | REGULATORS TO GWH-2, POOL HEATER, NOT SHOWN. |
| | |
| | I) LOW PRESSURE CSST SIZE OF 19 EHD SHALL BE INCREASED |
| | TO 25 EHD PER TABLE 402.4(15). |
| | |
| | J) LOCATION OF GWH-1 NOT SHOWN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |