2023-06-07 16:58:441ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23060136
 6/7/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P3.1 GAS RISER CORRECTIONS:
  
 A) TOTAL LOAD SHOWN ON RISER IS 1,721,700 BTUH, LOAD IN
 SCHEDULE IS 1,138,000.
  
 B) PIPE TYPE, SIZE, AND LENGTH FROM LOW PRESSURE
 REGULATOR TO GENERATOR NOT SHOWN.
  
 C) LOW PRESSURE REGULATOR BY GWH-2 NOT LABELED.
  
 D) LOW PRESSURE 1/2--INCH STEEL PIPE FOR A LOAD OF
 330,000 AT TOTAL DEVELOPED LENGTH OF 40 FT. IS
 UNDERSIZED PER TABLE 402.4(2). THE MINIMUM SIZE
 REQUIRED IS 1-1/4-INCH.
  
 E) LOW PRESSURE CSST LOAD OF 659,000 BTUH IS INCORRECT.
 THE LOAD SHOWN IS 140,000 BTUH.
  
 F) LOW PRESSURE CSST SIZE OF 25 EHD MUST BE INCREASED
 TO EHD 30 PER TABLE 402.4(15)
  
 G) LOW PRESSURE 1/2--INCH STEEL DROP TO 100,000 BTUH
 COOKTOP SHALL BE INCREASED TO 3/4-INCH- TABLE 402.4(2).
  
 H) PIPE TYPE, SIZE, AND LENGTH FROM LOW PRESSURE
 REGULATORS TO GWH-2, POOL HEATER, NOT SHOWN.
  
 I) LOW PRESSURE CSST SIZE OF 19 EHD SHALL BE INCREASED
 TO 25 EHD PER TABLE 402.4(15).
  
 J) LOCATION OF GWH-1 NOT SHOWN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  