Plan Review Notes
Plan Review Notes For Permit 23060115
Permit Number 23060115
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-06-06 10:31:19FIRE PROVISO:
  
 THERE IS A NOTE UNDER THE JOB SCOPE CONTRACT UNDER
 GUEST BEDROOM FOR THE "ALARM
 NEAR MASTER BATH DOOR " TO BE MOVED BY BUILDING
 MAINTENANCE WHICH IS NOT ALLOWED.
  
 THE FIRE ALARM SYSTEM SHALL BE MAINTAINED THROUGHOUT
 DEMO & CONSTRUCTION.
  
 ANY WORK/RELOCATION OF FA DEVICES/EQUIPMENT SHALL BE
 DONE BY A FIRE ALARM CONTRACTOR
 UNDER SEPARATE PERMIT & SHOP DRAWINGS.
  
  