| Date |
Text |
| 2023-06-07 13:39:17 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. SUBMITTED PRODUCT APPROVAL FL1654-R30 HAS BEEN |
| | REVISED TO FL1654-R31. PLEASE PROVIDE THE FOLLOWING: |
| | COVER PAGE, EVALUATION REPORT PAGES 1-5 AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. SUBMITTED |
| | FLORIDA DBPR PRODUCT APPROVAL FL1654-R30 SYSTEM NO. |
| | W-209 DO NOT MEET THE MINIMUM ZONE 3 DESIGN PRESSURE |
| | REQUIREMENT OF -131.42 FOR EXPOSURE CATEGORY D AREAS. |
| | PROVIDE SYSTEM THAT MEETS OR EXCEEDS ALL DESIGN |
| | PRESSURE REQUIREMENTS FOR EXPOSURE CATEGORY D/PROVIDE |
| | SIGNED AND SEALED ENGINEERED NAILING CALCULATIONS WITH |
| | AN APPROVED SYSTEM. |
| | 2. FBC B 107.2.1 FBC EB 706.1 SUBMITTED ROOF |
| | DRAWING/SKETCH LISTS FLAT/LOW ROOF SLOPE AS 0:12; LOW |
| | SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. PROVIDE METHOD |
| | OF PROVIDING POSITIVE DRAINAGE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |