| Plan Review Notes For Permit 23060023 |
| Permit Number |
23060023 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-07-18 14:29:04 | PRIVATE PROVIDER AUDIT | | | | | | AUDIT STATUS FAILED | | | | | | 1) THE EXPOSURE CATEGORY FOR THIS PROJECT IS C. PLEASE | | | REVISE THE DRAWINGS. FBC-R301.2.1.4.3 | | | | | | 2) SUBMIT A STRUCTURAL ANALYSIS OF THE EXISTING ROOF | | | STRUCTURE SHOWING THAT IT IS CAPABLE OF SUPPORTING ALL | | | LOADS TRANSFERRED TO IT BY THE PHOTOVOLTAIC SYSTEM. | | | FBC-R324.4.1 STRUCTURAL REQUIREMENTS. ROOFTOP-MOUNTED | | | PHOTOVOLTAIC PANEL SYSTEMS SHALL BE DESIGNED TO | | | STRUCTURALLY SUPPORT THE SYSTEM AND WITHSTAND | | | APPLICABLE GRAVITY LOADS IN ACCORDANCE WITH CHAPTER 3. | | | THE ROOF ON WHICH THESE SYSTEMS ARE INSTALLED SHALL BE | | | DESIGNED AND CONSTRUCTED TO SUPPORT THE LOADS IMPOSED | | | BY SUCH SYSTEMS IN ACCORDANCE WITH CHAPTER 8. | | | | | | FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | |
|