2023-06-07 12:45:211ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23051714
 6/7/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS SP-2.01 & SP-4.03: THE SPA SKIMMER GPM FLOW
 IS NOT SHOWN, AND RECIRCULATION FLOW SHALL BE 100%
 THROUGH THE MAIN DRAIN AND 60% THROUGH THE SKIMMER
 SYSTEM- SECS. 454.1.6.5.3 & 454.1.8.1 FBC B.
  
 2) SP-3.01, SP-3.02, SP-4.01 & SP-4.03: PLEASE SHOW THE
 LOCATION OF THE COLD SPA COLLECTOR TANK AND PIPING
 CONNECTIONS AND DETAILS- SECS. 454.1.6.5.10.5 &
 454.1.8.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  