Plan Review Notes
Plan Review Notes For Permit 23051712
Permit Number 23051712
Review Stop P
Sequence Number 1
Notes
Date Text
2023-06-07 11:47:381ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23051712
 6/7/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS SP-1.07, SP-1.10, SP-4.03: THE GPM FLOW OF
 THE GUTTER SYSTEM IS NOT SHOWN, AND RECIRCULATION FLOW
 SHALL BE 100% THROUGH THE MAIN DRAIN AND 100% THROUGH
 THE PERIMETER OVERFLOW SYSTEM- SEC. 454.1.6.5.3 FBC B.
  
 2) SP-1.07: PLEASE SHOW THE SPACING BETWEEN THE 3-IN.
 GUTTER DRAINS WILL NOT EXCEED 15 FT.- SEC.
 454.1.6.5.3.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  