Plan Review Notes
Plan Review Notes For Permit 23051712
Permit Number 23051712
Review Stop G
Sequence Number 1
Notes
Date Text
2023-06-07 11:54:571ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23051712
 6/7/2023
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS SP-1.09, SP-4.01 & SP-4.02: SHEET SP-1.09
 DRAWING MUST BE REVISED TO SHOW 4 POOL HEATERS BASED ON
 THE EQUIPMENT SCHEDULE AND THE APPROVED DRAWINGS UNDER
 THE MASTER PERMIT 22050891.
  
 2) NO GAS PLANS FOR INSTALLATION OF THE POOL HEATERS
 AND PIPING WERE INCLUDED IN THE SUBMITTAL. PLEASE
 CLARIFY IF THE INSTALLATIONS INCLUDING THE PIPING,
 COMBUSTION AIR AND VENTING SYSTEMS WILL BE COMPLETED
 UNDER THIS PERMIT OR UNDER THE BUILDING GAS SUB-PERMIT
 22101410. PLEASE NOTE IF THE FIRST OPTION IS SELECTED
 THEN COMPLETE PLANS AND DETAILS SHALL BE SUBMITTED AND
 A GAS SUB-PERMIT APPLICATION SHALL BE PROVIDED- SEC.
 107.2.1 & 107.3.5.1.5 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  