| 2023-06-05 08:29:05 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. SUBMITTED MIAMI-DADE COUNTY NOA 21-1130.01 COVERS |
| | MULTIPLE PRODUCTS & INSTALLATION PROCEDURES: SYSTEMS |
| | TYPE E(1) THROUGH F(1). SELECT PRODUCT & INSTALLATION |
| | PROCEDURE TO BE USED. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. |
| | 2. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED ASPHALT SHINGLE |
| | ROOFING SYSTEM TO BE USED. INCLUDE COVER PAGE, |
| | EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR |
| | SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| | DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY |
| | COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC |
| | ENGINEERING. SUBMITTED MIAMI-DADE NOA NO. 21-0518.04 |
| | LIMITATION #2 SHALL NOT BE INSTALLED ON ROOF HEIGHTS IN |
| | EXCESS OF 33FT. SUBMITTED ROOF DIAGRAM LISTS MEAN ROOF |
| | HEIGHT 30 FT. A THREE-STORY COMMERCIAL BUILDING WITH A |
| | 6:12 ROOF SLOPE MEAN ROOF HEIGHT @ A MINIMUM WILL BE 40 |
| | FT. |
| | 3. FBC B 107.2.1. PLEASE VERIFY & CORRECT; SUBMITTED |
| | ROOF DIAGRAM/SKETCH SHOWS BUILDING ADDRESS AS 3101 |
| | VILLAGE BLVD, PERMIT APPLICATION IS FOR 3151 VILLAGE |
| | BLVD. |
| | 4.FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE IS |
| | LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO WALL |
| | CONNECTIONS WILL BE IMPROVED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |