| 2023-06-01 10:07:43 | FIRE PROVISO: | | | | | | FIRE SPRINKLER PIPE INSPECTION ALSO REQUIRED | | | CODE: 603 | | | | | | CITY OF WEST PALM BEACH | | | | | | PERMIT # 23051632 | | | | | | TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13 | | | | | | CONTRACTOR TO PROVIDE FOR WORKING PRESSURE VERIFICATION | | | (I.E. PRESSURE GAUGE 2HRS) AND/OR SYSTEM IS CHARGED/ | | | DISCHARGED UNDER WORKING PRESSURE. (I.E. VISUAL FOR | | | LEAKS | | | & INSPECTOR DRAIN AFTER 2 HRS) | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|