| 2023-06-06 10:45:22 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF A 10 X 30 CHICKEE HUT W NO |
| | ELECTIC NOR PLUMBING; HOWEVER, THERE IS NO INDICATED |
| | PURPOSE NOR USE OF THE PROPOSED. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE OCCUPANCY |
| | CLASSIFICATION PER THE FLORIDA FIRE PREVENTION CODE AND |
| | ANY APPLICABLE FLOOR PLANS INCLUDING |
| | TABLES/CHAIRS, FURNITURE, PLANTERS, LANDCAPE, ETC. |
| | UNDER IT. |
| | |
| | |
| | |
| | 2) THERE IS AN INDICATION ON THE SURVEY OF THE HUT 5 ' |
| | FROM THE EAST BUILDING AND WHAT APPEARS TO BE LESS FROM |
| | THE EXISTING SITE BUILDING BUT NO INDICATION HOW THIS |
| | PROPOSED LOCATION AFFECTS THE EXISTING EXITING OF THE |
| | EXISTING BUILDING. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | PLEASE PROVIDE A LIFE SAFETY PLAN SHEET INDICATING |
| | COMPLIANCE |
| | |
| | |
| | |
| | 3) THERE IS AN INDICATION OF AN APPARENT COMBUSTIBLE |
| | VEGETATION HUT, BUT NO INDICATION OF PROPOSED FIRE |
| | PROTECTION/FIRE RETARDANT CERTIFICATION. |
| | |
| | 4.6 GENERAL REQUIREMENTS |
| | |
| | 4.6.1 AUTHORITY HAVING JURISDICTION. |
| | |
| | 4.6.1.1 THE AUTHORITY HAVING JURISDICTION SHALL |
| | DETERMINE WHETHER THE |
| | PROVISIONS OF THIS CODE ARE MET. |
| | |
| | 4.6.1.2 ANY REQUIREMENTS THAT ARE ESSENTIAL FOR THE |
| | SAFETY OF BUILDING |
| | OCCUPANTS AND THAT ARE NOT SPECIFICALLY PROVIDED FOR BY |
| | THIS CODE SHALL |
| | BE DETERMINED BY THE AUTHORITY HAVING JURISDICTION |
| | |
| | 4.6.1.3 WHERE IT IS EVIDENT THAT A REASONABLE DEGREE OF |
| | SAFETY IS PROVIDED, |
| | ANY REQUIREMENT SHALL BE PERMITTED TO BE MODIFIED IF, |
| | IN THE JUDGMENT |
| | OF THE AUTHORITY HAVING JURISDICTION, ITS APPLICATION |
| | WOULD BE HAZARDOUS |
| | UNDER NORMAL OCCUPANCY CONDITIONS. |
| | |
| | PLEASE PROVIDE FOR THE INTENT TO APPLY/INSTALL A FIRE |
| | RETARDANT CERTICATION BY A QUALIFIED LICENSED CONTRATOR |
| | TO THIS STRUCTURE. |
| | |
| | |
| | |
| | 4) FOR INFORMATIONAL PURPOSES; |
| | |
| | NO COOKING, BBQS, OPEN FLAMES NOR PROPANE HEATERS WILL |
| | BE ALLOWED UNDER THE HUT WITHOUT PRIOR REVIEW AND |
| | APPROVAL |
| | AND/OR PERMITTING IF APPLICABLE. |
| | |
| | WARMING OF FOOD IS ACCEPTABLE, ENSURE NO COMBUSTIBLES |
| | NEAR WARMING DEVICES. |
| | |
| | NO PYROTECHNICS/FLAME EFFECTS ON STAGE IN OR AROUND THE |
| | HUT WITHOUT PROPER FIREWORKS APPLICATION |
| | APPROVAL BY THE FIRE MARSHAL. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |