| Date |
Text |
| 2023-06-02 11:04:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS NO INDICATION ON THE SCOPE OF WORK OF FLOOR |
| | TILE AND FLOOR COVERING ON THE CONTRACT; HOWEVER, THE |
| | IS FLOORING TYPE NOR A PRODUCT NAME AND IF APPLICABLE, |
| | A MANUFACTURER'S SPECIFICATION SHEET. |
| | |
| | TILE FLOORING OR FLOOR COVERING CAN HAVE DIFFERENT |
| | MEANINGS BUT FIOORING IS MANUFACTURED AROUND THE WORLD |
| | BUT NOT ALL ARE TESTED AND MEETING LISTED AND NFPA |
| | STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING |
| | TYPE, PRODUCT NAME AND, IF APPLICABLE, THE PRODUCT SPEC |
| | SHEETS INDICATING THE FIRE BEHAVIOR RATING. |
| | |
| | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| | WOULD NOT BE REQUIRED. |
| | |
| | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| | FLOORING, WOOD/VINYL LAMINATES, ETC. |
| | |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |