| 2023-06-01 14:54:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET A0.2 & A2.0- THERE ARE INDICATIONS OF A SINGLE |
| | DOOR ALONG THE FRONT FENCE OF THE SIDE YEARD OUTSIDE |
| | SEATING AREA. THE DOOR IS INDICATED AS SWINGING INWARD. |
| | |
| | PREVIOUS APPROVED PLANS ON RECORD 16050258 SHOWED DOORS |
| | SWINGING OUTWARD. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS, |
| | |
| | 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| | REQUIRED TO BE OF |
| | THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN |
| | THE DIRECTION |
| | OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| | OF 50 OR MORE, |
| | EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| | REQUIRED TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY |
| | 7.2.4.3.8.1 |
| | OR 7.2.4.3.8.2. |
| | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| | TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH |
| | CARE OCCUPAN CIES, AS PROVIDED IN CHAPTER 19. |
| | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| | ENCLOSURE, UNLESS THE |
| | DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| | OPENS DIRECTLY |
| | INTO AN EXIT ENCLOSURE |
| | |
| | |
| | (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD |
| | CONTENTS AREA |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 2) SHEET A2.0 & A5.0 - THERE ARE INDICATIONS OF |
| | GATES/DOORS ON THE EXTEIOR FENCES OF THE OUTSIDE AREA |
| | THAT ARE INDICATED AND REQUIRED AS EXITS. |
| | |
| | THE ARE NO INDICATIONS ON THE DOOR SCHEDULE OF THE EXIT |
| | HARDWARE/LOCKS/LATCHES THAT ARE IN COMPLINACE WITH THE |
| | REQUIREMENTS OF NFPA 101 CH 7 MEANS OF EGRESS. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 3) SHEET M1.1A - THERE ARE INDICATIONS OF NEW HOOD |
| | WORK. |
| | |
| | ANY WORK ON THE HOOD SYSTM SHALL BE UNER SEPARATE |
| | PERMIT & SHOP DRAWINGS PER NFPA 96. |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF |
| | ACKNOWLGMENT ON THE PLAN. |
| | |
| | |
| | |
| | 4) SHEET A0.2 & A2.0 - THE OCCUPNACY HAS AN EXISTING |
| | FIRE SPRINKLER AND FIRE ALARM SYSTEM. |
| | |
| | THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| | DEMO AND CONSTRUCTION. |
| | |
| | PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND |
| | EQUIPMENT. |
| | |
| | DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM |
| | DEVICES/EQUIPMENT. |
| | |
| | ANY WORK/DAMAGE ON THE FS/FA SYSTEMS SHALL BE |
| | CORRECTED/REPAIRED PER NFPA 13 & 72, UNDER SEPARATE |
| | PERMIT AND SHOP DRAWING BY FS/FA CONTRACTORS |
| | |
| | PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A |
| | NOTE OF ACKNOWLEDGMENT ON THE FLOOR & LIFE SAFETY PLAN. |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |