| 2023-06-21 12:19:46 | 2ND REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23051386 |
| | 6/21/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) NEW GAS RISER: PLEASE IDENTIFY THE PIPING AS EITHER |
| | SCHEDULE 40 METALLIC, COPPER, PE, OR CSST PER SEC. |
| | G2414.1 FBC RES. FLEX IS NOT AN APPROVED MATERIAL. IF |
| | THE PIPING IS CSST, PLEASE PROVIDE THE EHD OF THE |
| | PIPING AS REQUIRED BY TABLES G2413.4(16) & G2413.17 FBC |
| | RES. |
| | |
| | A) THE SPECS FOR THE WATER HEATER INDICATE THE REQUIRED |
| | INPUT PRESSURE IS 3.5" TO 10.5" WC HOWEVER THE PRESSURE |
| | AT THE METER IS 2 P.S. I. WHICH REQUIRES INSTALLATION |
| | OF A STEP-DOWN REGULATOR. PLEASE SHOW THE REGULATOR ON |
| | THE RISER AND CORRECT THE NOTES INDICATING THE |
| | REGULATOR IS INTEGRAL TO THE WATER HEATER- SEC. G2421.2 |
| | FBC RES. |
| | |
| | 2) THE WATER HEATER SHALL BE INSTALLED A MINIMUM OF 4 |
| | FT. FROM THE WINDOW OPENINGS REGARDLESS IF THE WINDOWS |
| | ARE BOARDED UP. PLEASE SHOW THE CLEARANCE DISTANCES ON |
| | THE PLAN- SEC. G2427.8 FBC RES. |
| | |
| | 3) AS PREVIOUSLY REQUESTED, PROVIDE THE PIPE SIZING |
| | TABLES USED- SEC. G2413.4. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |