Plan Review Notes
Plan Review Notes For Permit 23051386
Permit Number 23051386
Review Stop G
Sequence Number 2
Notes
Date Text
2023-06-21 12:19:462ND REVIEW FBC-2020 RES. GAS
 PERMIT- 23051386
 6/21/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NEW GAS RISER: PLEASE IDENTIFY THE PIPING AS EITHER
 SCHEDULE 40 METALLIC, COPPER, PE, OR CSST PER SEC.
 G2414.1 FBC RES. FLEX IS NOT AN APPROVED MATERIAL. IF
 THE PIPING IS CSST, PLEASE PROVIDE THE EHD OF THE
 PIPING AS REQUIRED BY TABLES G2413.4(16) & G2413.17 FBC
 RES.
  
 A) THE SPECS FOR THE WATER HEATER INDICATE THE REQUIRED
 INPUT PRESSURE IS 3.5" TO 10.5" WC HOWEVER THE PRESSURE
 AT THE METER IS 2 P.S. I. WHICH REQUIRES INSTALLATION
 OF A STEP-DOWN REGULATOR. PLEASE SHOW THE REGULATOR ON
 THE RISER AND CORRECT THE NOTES INDICATING THE
 REGULATOR IS INTEGRAL TO THE WATER HEATER- SEC. G2421.2
 FBC RES.
  
 2) THE WATER HEATER SHALL BE INSTALLED A MINIMUM OF 4
 FT. FROM THE WINDOW OPENINGS REGARDLESS IF THE WINDOWS
 ARE BOARDED UP. PLEASE SHOW THE CLEARANCE DISTANCES ON
 THE PLAN- SEC. G2427.8 FBC RES.
  
 3) AS PREVIOUSLY REQUESTED, PROVIDE THE PIPE SIZING
 TABLES USED- SEC. G2413.4.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  