Plan Review Notes
Plan Review Notes For Permit 23051386
Permit Number 23051386
Review Stop G
Sequence Number 1
Notes
Date Text
2023-06-12 14:12:241ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23051386
 6/12/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GAS RISER IS INCOMPLETE. PLEASE PROVIDE THE
 FOLLOWING INFORMATION- SEC. 107.3.5.3 WPB AND SECS.
 G2412.4 & G2413.1 FBC RES.
 A) SHOW THE LOCATION OF THE METER AND DELIVERY
 PRESSURE.
 B) SHOW THE INDIVIDUAL BTU LOADS OF THE EXISTING RANGE,
 POOL HEATER AND THE NEW WATER HEATER, AND THE TOTAL
 LOAD OF THE SYSTEM.
 C) SHOW THE BRANCH PIPING LENGTH MEASUREMENTS AND THE
 TOTAL DEVELOPED LENGTH OF THE PIPING RUN FROM THE METER
 TO THE MOST REMOTE APPLIANCE.
 D) SHOW THE LOCATIONS OF REGULATORS AND OUTLET
 PRESSURES.
 E) PROVIDE THE PIPE SIZING TABLES USED.
  
 2) SHOW THE CLEARANCE DISTANCE MEASUREMENTS FROM THE
 WATER HEATER EXHAUST TO AIR INTAKES AND OPERABLE
 OPENINGS INTO THE HOUSE- SECS. G2427.8 & G2448.1 FBC
 RES.
  
 3) SIGNATURE OF THE CONTRACTOR OR QUALIFIER SHALL BE ON
 THE DRAINGS- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  