| 2023-06-12 14:12:24 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23051386 |
| | 6/12/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE GAS RISER IS INCOMPLETE. PLEASE PROVIDE THE |
| | FOLLOWING INFORMATION- SEC. 107.3.5.3 WPB AND SECS. |
| | G2412.4 & G2413.1 FBC RES. |
| | A) SHOW THE LOCATION OF THE METER AND DELIVERY |
| | PRESSURE. |
| | B) SHOW THE INDIVIDUAL BTU LOADS OF THE EXISTING RANGE, |
| | POOL HEATER AND THE NEW WATER HEATER, AND THE TOTAL |
| | LOAD OF THE SYSTEM. |
| | C) SHOW THE BRANCH PIPING LENGTH MEASUREMENTS AND THE |
| | TOTAL DEVELOPED LENGTH OF THE PIPING RUN FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE. |
| | D) SHOW THE LOCATIONS OF REGULATORS AND OUTLET |
| | PRESSURES. |
| | E) PROVIDE THE PIPE SIZING TABLES USED. |
| | |
| | 2) SHOW THE CLEARANCE DISTANCE MEASUREMENTS FROM THE |
| | WATER HEATER EXHAUST TO AIR INTAKES AND OPERABLE |
| | OPENINGS INTO THE HOUSE- SECS. G2427.8 & G2448.1 FBC |
| | RES. |
| | |
| | 3) SIGNATURE OF THE CONTRACTOR OR QUALIFIER SHALL BE ON |
| | THE DRAINGS- SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |