Plan Review Notes
Plan Review Notes For Permit 23051267
Permit Number 23051267
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-05-30 15:13:06THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET ALS 1.1 - THERE IS AN INDICATION OF BUSINESS
 OCCUPANCY; HOWEVER, THE OCCUPANCY CLASSIFICATION
 APPAERS TO MIXED NONSEPARATED DUE TO THEIR BEING
 SEVERAL ASSEMBLY AREAS: RECEPTION/LOBBY,
 WAITING AREA, LOUNGE/THINK LIVING AREA, RECETION 2,
 STAGE AREA WITH TABLES & CHAIRS.
  
 PER NFPA 101 CH 6,
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF
 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ??? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ??? 6.1.14.4
  
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO
 OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE OCCU PANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE BARRIERS.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE
 IN ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE REQUIRE MENTS OF THE OCCUPANCIES INVOLVED,
 UNLESS SEPARATE SAFEGUARDS ARE
 APPROVED.
  
 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER OCCU PANCY, THE MULTIPLE OCCUPANCY
 SHALL BE TREATED AS A MIXED
  
 PLEASE REVIEW AND CORRECT AS THE ASSEMBLY AREAS IS
 REQUIRED TO BE CALCULATED PER NFPA 101 CH 7 OR PROVIDE
 DETAILED NARRATIVE AND FIRE CODE REFERENCES
  
  
 1A) PER # 1 ABOVE THE OCCUPANCY LOAD CALCULATION WOULD
 CHANGE AND ALSO THE EXITING REQUIREMENTS, DOOR SWINGS,
 EXIT HARDWARE, ETC, PER NFPA 101 CH 7 MEANS OF EGRESS.
  
  
 PLEASE REVIEW AND CORRECT OR PROVIDE DETAILED NARRATIVE
 AND FIRE CODE REFERENCES
  
  
  
 1B) PER # 1 & 2 ABOVE, AN ASSEMBLY AREA REQUIRES 2
 EXITS, PER NFPA 101, CH 12 AND CH 7.
  
 12.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE
 WITH CHAPTER 7 AND
 THIS CHAPTER.
  
 12.2.4* NUMBER OF MEANS OF EGRESS
  
 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4, OTHER THAN EXITS FOR FENCED OUTDOOR
 ASSEMBLY OCCUPANCIES
 IN ACCORDANCE WITH 12.2.4.4
  
 7.4.1 GENERAL.
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE,
 STORY, OR PORTION THEREOF SHALL BE NOT LESS THAN TWO,
 EXCEPT UNDER ONE OF
 THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED IN
 CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE OR
 BALCONY WHERE THE COMMON PATH OF TRAVEL LIMITATIONS OF
 CHAP TERS 11 THROUGH 43 ARE MET
  
 THE FLOOR PALN SHOWS 2 EXITS BUT THEY ARE NOT
 ACCESSIBLE WITH EACH OTHER.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE DETAILED NARRATIVE
 AND FIRE CODE REFERENCES
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  