| Date |
Text |
| 2023-06-01 10:52:11 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. SUBMITTED PRODUCT APPROVAL FL1654-R30 HAS BEEN |
| | REVISED TO FL1654-R31. PLEASE PROVIDE THE FOLLOWING: |
| | COVER PAGE, EVALUATION REPORT PAGES 1-5 AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER |
| | RULE 61G20-3. |
| | 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL27499.1-R4 INSTALLATION OPTION #1 MAXIMUM |
| | DESIGN PRESSURE -116 PSF. DO NOT MEET THE MINIMUM ZONE |
| | 3 DESIGN PRESSURE REQUIREMENT OF -121 FOR EXPOSURE |
| | CATEGORY C AREAS WITH A GABLE ROOF; ROOF SLOPES |
| | 2/12-4/12 MEAN ROOF HEIGHT UP TO 15 FT. SELECT OPTION |
| | THAT MEETS OR EXCEEDS THIS REQUIREMENT. ALL APPLICABLE |
| | DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON |
| | THE PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS |
| | NOT SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |