| 2023-05-25 16:01:48 | SPOKE WITH APPLICANT 6/2/23 10:30AM, HE STATED THAT |
| | THEY HAVE ANY EXISTING FLOORING PERMIT 22111032 THAT |
| | WAS APPROVED AND IS RELATED TO THIS PERMIT AND |
| | SHOULD HAVE BEEN INDICATED ON THIS PERMIT. |
| | |
| | FLOORING COMMENT ADDRESSED. |
| | |
| | COMMNETS 2 & 3 WILL BE CHANGED TO PROVISO, 4 & 5 NO |
| | LONGER APPLY: APPLICANT ACKNOWLEDGED. |
| | |
| | FIRE PROVISO: |
| | |
| | 1) THERE ARE INDICATIONS OF BATHROOM WORK THAT MAY |
| | INVOLVE REQUIRED NFPA FIRE RATED TENANT/CORRIDOR |
| | SEPARATION WALLS. |
| | |
| | ENSURE FIRE RATED TENANT SEPARATION WALLS, IF DAMAGED, |
| | ARE REPAIRED TO THE EXISTING FIRE RATED SEPARATION. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT ON |
| | THE PLAN SHEET. |
| | |
| | |
| | |
| | 2 ) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND |
| | EQUIPMENT. |
| | |
| | DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM |
| | DEVICES/EQUIPMENT. |
| | |
| | THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| | DEMO AND CONSTRUCTION. |
| | |
| | PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A |
| | NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | ******************************************************* |
| | ******************************************************* |
| | ****************************** |
| | |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS NO INDICATION OF A FLOORING TYPE, |
| | MANUFACTURER'S SPECIFICATION SHEET NOR A PRODUCT NAME. |
| | |
| | FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT ALL |
| | ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING |
| | TYPE THE PRODUCT ANMCE AND SPEC SHEETS INDICATING THE |
| | FIRE BEHAVIOR RATING. |
| | |
| | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| | WOULD NOT BE REQUIRED. |
| | |
| | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| | FLOORING, WOOD/VINYL LAMINATES, ETC. |
| | |
| | |
| | |
| | 2) THERE ARE INDICATIONS OF BATHROOM WORK THAT MAY |
| | INVOLVE REQUIRED NFPA FIRE RATED TENANT/CORRIDOR |
| | SEPARATION WALLS. |
| | |
| | ENSURE FIRE RATED TENANT SEPARATION WALLS, IF DAMAGED, |
| | ARE REPAIRED TO THE EXISTING FIRE RATED SEPARATION. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT ON |
| | THE PLAN SHEET. |
| | |
| | |
| | |
| | 3) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND |
| | EQUIPMENT. |
| | |
| | DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM |
| | DEVICES/EQUIPMENT. |
| | |
| | THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| | DEMO AND CONSTRUCTION. |
| | |
| | PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A |
| | NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |