2023-06-20 02:04:13ELECTRIC REVIEW FAILED
  
 1) ALL MEP DRAWINGS DO NOT DETAIL THE REQUIRED DIGITAL
 SIGNATURE AS REQUIRED. PLEASE CORRECT AS OUTLINED
 BELOW.
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
  
 2) PLEASE DETAIL FIXED WALL RECEPTACLES IN ACCORDANCE
 WITH NEC 210.71 MEETING ROOMS
 (B) RECEPTACLE OUTLETS REQUIRED.
 THE TOTAL NUMBER OF RECEPTACLE OUTLETS, INCLUDING FLOOR
 OUTLETS AND RECEPTACLE OUTLETS IN FIXED FURNITURE,
 SHALL NOT BE LESS THAN AS DETERMINED IN (1) AND (2).
 THESE RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE
 LOCATED AS DETERMINED BY THE DESIGNER OR BUILDING
 OWNER.
 (1) RECEPTACLE OUTLETS IN FIXED WALLS.
 RECEPTACLE OUTLETS SHALL BE INSTALLED IN ACCORDANCE
 WITH 210.52(A)(1) THROUGH (A)(4)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  