| 2023-06-20 02:04:13 | ELECTRIC REVIEW FAILED |
| | |
| | 1) ALL MEP DRAWINGS DO NOT DETAIL THE REQUIRED DIGITAL |
| | SIGNATURE AS REQUIRED. PLEASE CORRECT AS OUTLINED |
| | BELOW. |
| | |
| | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF |
| | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| | DIGITALLY SEALED AND SIGNED. |
| | |
| | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS |
| | FOLLOWING PROJECTDOX INSTRUCTIONS |
| | |
| | |
| | 2) PLEASE DETAIL FIXED WALL RECEPTACLES IN ACCORDANCE |
| | WITH NEC 210.71 MEETING ROOMS |
| | (B) RECEPTACLE OUTLETS REQUIRED. |
| | THE TOTAL NUMBER OF RECEPTACLE OUTLETS, INCLUDING FLOOR |
| | OUTLETS AND RECEPTACLE OUTLETS IN FIXED FURNITURE, |
| | SHALL NOT BE LESS THAN AS DETERMINED IN (1) AND (2). |
| | THESE RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE |
| | LOCATED AS DETERMINED BY THE DESIGNER OR BUILDING |
| | OWNER. |
| | (1) RECEPTACLE OUTLETS IN FIXED WALLS. |
| | RECEPTACLE OUTLETS SHALL BE INSTALLED IN ACCORDANCE |
| | WITH 210.52(A)(1) THROUGH (A)(4) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |