2023-06-28 08:48:27WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23051198
 ADD: 525 OKEECHOBEE BLVD # 1200
 CONT: BUTLER CONSTRUCTION
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 28TH/ 2023
 ACTION: DENIED
  
 1) SHEET A0-01 INDEX & PROJECT INFORMATION.
 1A) CODE ANALYSIS II APPLICABLE BUILDING CODES LIST A-L
 CODES, THE FLORIDA FAMILY OF CODES AS THE FLORIDA 2017
 CODES SIXTH EDITION. PLEASE UPDATE TO THE 2020 FBC
 (FAMILY OF CODE) 7TH EDITION. THE STATE OF FLORIDA
 ADOPTED STATEWIDE ON DEC. 31/2020 THE 7TH EDITION OF
 THE FLORIDA CODES.
  
 2) IV GENERAL BUILDING FEATURES LIST EVERYTHING IN THE
 IBC, AGAIN WE ARE IN THE 7TH EDITION OF THE FLORIDA
 BUILDING CODES.
  
 3) SHEET A3-12 POWER & COMMUNICATION PLAN SHOWS SYMBOLS
 F-1 ??? F-4 NEW STUB UP CONDUITS THAT WILL REQUIRE CORE
 DRILLING OF THE POST TENSION FLOORS. THERE IS NO
 MENTION OF POST TENSION FLOORS THAT ARE TO HAVE
 PENETRATION OF THE CONCRETE ARE REQUIRED TO HAVE THE
 SLAB X-RAYED TO LOCATE TENDONS. CONFORMANCE. 2020
 EXISTING BUILDING CODE, LEVEL-1 ALTERATION 701.2,
 LEVEL-2 ALTERATION 801.3, & LEVEL-3 ALTERATIONS
 901.2COMPLIANCE. AN EXISTING BUILDING OR PORTION
 THEREOF SHALL NOT BE ALTERED SUCH THAT THE BUILDING
 BECOMES LESS SAFE THAN ITS EXISTING CONDITION.
 4) SHEET A3-12 POWER & COMMUNICATION PLAN SHOWS SYMBOLS
 F-1 ??? F-4 NEW STUB UP CONDUITS THAT WILL PENETRATE
 THE FIRE RATED CONCRETE SLAB. SHEET A7-02 UL DETAILS DO
 NOT HAVE ASSEMBLIES FOR THE FLOOR PENETRATIONS. 2020
 FBC-BUILDING CODE SECTION 714.4.1.2 THROUGH-PENETRATION
 FIRESTOP SYSTEM.
 5) NEITHER SHEETS A1-12 OR A0-21 SHOW EITHER A SIDE
 APPROACH OR FRONT APPROACH TO THE BREAK ROOM SINK OR
 MICROWAVE. PLEASE SHOW COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE SECTIONS:
 305.4 KNEE AND TOE CLEARANCES.
 305.5 POSITION.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  