| Date |
Text |
| 2023-06-28 08:48:27 | WEST PALM BEACH DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 23051198 |
| | ADD: 525 OKEECHOBEE BLVD # 1200 |
| | CONT: BUTLER CONSTRUCTION |
| | TEL: 561-832-9700 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JUNE 28TH/ 2023 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A0-01 INDEX & PROJECT INFORMATION. |
| | 1A) CODE ANALYSIS II APPLICABLE BUILDING CODES LIST A-L |
| | CODES, THE FLORIDA FAMILY OF CODES AS THE FLORIDA 2017 |
| | CODES SIXTH EDITION. PLEASE UPDATE TO THE 2020 FBC |
| | (FAMILY OF CODE) 7TH EDITION. THE STATE OF FLORIDA |
| | ADOPTED STATEWIDE ON DEC. 31/2020 THE 7TH EDITION OF |
| | THE FLORIDA CODES. |
| | |
| | 2) IV GENERAL BUILDING FEATURES LIST EVERYTHING IN THE |
| | IBC, AGAIN WE ARE IN THE 7TH EDITION OF THE FLORIDA |
| | BUILDING CODES. |
| | |
| | 3) SHEET A3-12 POWER & COMMUNICATION PLAN SHOWS SYMBOLS |
| | F-1 ??? F-4 NEW STUB UP CONDUITS THAT WILL REQUIRE CORE |
| | DRILLING OF THE POST TENSION FLOORS. THERE IS NO |
| | MENTION OF POST TENSION FLOORS THAT ARE TO HAVE |
| | PENETRATION OF THE CONCRETE ARE REQUIRED TO HAVE THE |
| | SLAB X-RAYED TO LOCATE TENDONS. CONFORMANCE. 2020 |
| | EXISTING BUILDING CODE, LEVEL-1 ALTERATION 701.2, |
| | LEVEL-2 ALTERATION 801.3, & LEVEL-3 ALTERATIONS |
| | 901.2COMPLIANCE. AN EXISTING BUILDING OR PORTION |
| | THEREOF SHALL NOT BE ALTERED SUCH THAT THE BUILDING |
| | BECOMES LESS SAFE THAN ITS EXISTING CONDITION. |
| | 4) SHEET A3-12 POWER & COMMUNICATION PLAN SHOWS SYMBOLS |
| | F-1 ??? F-4 NEW STUB UP CONDUITS THAT WILL PENETRATE |
| | THE FIRE RATED CONCRETE SLAB. SHEET A7-02 UL DETAILS DO |
| | NOT HAVE ASSEMBLIES FOR THE FLOOR PENETRATIONS. 2020 |
| | FBC-BUILDING CODE SECTION 714.4.1.2 THROUGH-PENETRATION |
| | FIRESTOP SYSTEM. |
| | 5) NEITHER SHEETS A1-12 OR A0-21 SHOW EITHER A SIDE |
| | APPROACH OR FRONT APPROACH TO THE BREAK ROOM SINK OR |
| | MICROWAVE. PLEASE SHOW COMPLIANCE WITH THE 2020 |
| | FBC-ACCESSIBILITY CODE SECTIONS: |
| | 305.4 KNEE AND TOE CLEARANCES. |
| | 305.5 POSITION. |
| | |
| | 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT |
| | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |