| 2023-07-05 10:19:50 | RESIDENTIAL(R3) REROOF FIFTH BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23051185 |
| | 1827 PINEHURST DR |
| | |
| | PREVIOUS COMMENT: |
| | 2-RAS 117 CALCULATIONS SUBMITTED: |
| | REVISED CALCULATIONS STILL SHOW THE DESIGN PRESSURES |
| | LOWER THAN THE DESIGN PRESSURES SHOWN ON THE FIRST |
| | CALCULATIONS SUBMITTED WHEN THE BUILDING EXPOSURE WAS |
| | ASSUMED TO BE EXPOSURE B. REVISE AS REQUIRED. |
| | ENGINEER TO CLARIFY WHY THE DESIGN PRESSURES ARE SO LOW |
| | COMPARED TO TABLE R301.2(2) AND TABLE R301.2(2) |
| | FBC-RESIDENTIAL. |
| | ALSO, ENGINEER TO PROVIDE THE DESIGN PRESSURES FOR ALL |
| | FOUR ROOF ZONES. |
| | SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY |
| | AMENDMENTS. |
| | |
| | RESPONSE: |
| | CALCULATIONS WERE REVISED AND FASTENER SPACING |
| | SPECIFIED FOR ZONE 1' DOESN'T MATCH FASTENER SPACING |
| | FOR FASTENING OPTION #2 FOR -52.5 PSF SHOWN ON NOA |
| | 18-0919.12 AS SPECIFIED BY THE ENGINEER ON PAGE 2 OF |
| | WIND UPLIFT CALCULATIONS SUBMITTED. REVISE AS REQUIRED |
| | TO MATCH. NOTE: COORDINATE ENHANCED NAILING FOR THE |
| | OTHER ZONES AS REQUIRED. |
| | SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY |
| | AMENDMENTS. |
| | |
| | 3- DIGITAL SIGNATURE REVIEW: |
| | A)ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| | REQUIREMENTS OF FBPE. THE TEXT BOX LANGUAGE MUST BE |
| | IDENTICAL TO THE SAMPLES PUBLISHED BY FBPE. SEE FBPE.OR |
| | G/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCUMENTS/... |
| | AND REVISE AS REQUIRED TO MATCH. |
| | NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR. |
| | |
| | B)IT IS NOT CLEAR IF THE DOCUMENT IS DIGITALLY SIGNED |
| | OR ELECTRONICALLY SIGNED. CHECK THE TEXT BOX LANGUAGE . |
| | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU |
| | MENTS/... |
| | |
| | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | 61G15-23.005 PROCEDURES FOR ELECTRONICALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |