| Plan Review Notes For Permit 23051185 |
| Permit Number |
23051185 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2023-06-27 15:36:41 | RESIDENTIAL(R3) REROOF FOURTH BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #23051185 | | | 1827 PINEHURST DR | | | | | | PREVIOUS COMMENT: | | | 2-RAS 117 CALCULATIONS SUBMITTED: | | | ENGINEER TO CLARIFY WHY THE DESIGN PRESSURES SHOWN ON | | | THE REVISED RAS 117 CALCULATIONS ARE LOWER FOR BUILDING | | | EXPOSURE "C" THAN THE DESIGN PRESSURES GIVEN FOR | | | EXPOSURE "B". DESIGN PRESSURES CAN NOT BE LOWER. | | | PROVIDE CALCULATIONS. | | | SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY | | | AMENDMENTS. | | | | | | RESPONSE: | | | REVISED CALCULATIONS STILL SHOW THE DESIGN PRESSURES | | | LOWER THAN THE DESIGN PRESSURES SHOWN ON THE FIRST | | | CALCULATIONS SUBMITTED WHEN THE BUILDING EXPOSURE WAS | | | ASSUMED TO BE EXPOSURE B. REVISE AS REQUIRED. | | | ENGINEER TO CLARIFY WHY THE DESIGN PRESSURES ARE SO LOW | | | COMPARED TO TABLE R301.2(2) AND TABLE R301.2(2) | | | FBC-RESIDENTIAL. | | | ALSO, ENGINEER TO PROVIDE THE DESIGN PRESSURES FOR ALL | | | FOUR ROOF ZONES. | | | SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY | | | AMENDMENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|