| Notes |
| Date |
Text |
| 2023-06-20 10:12:03 | RESIDENTIAL(R3) REROOF THIRD BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #23051185 | | | 1827 PINEHURST DR | | | | | | 2- FLAT ROOF NOA 18-0919.12 SUBMITTED: SELECTED | | | ASSEMBLY SYSTEM TYPE E(4) ON PAGE 57 OF 67 DOESN'T MEET | | | THE DESIGN PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED | | | AND SEALED RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7 ON LAST PAGE OF NOA. NEED THE | | | CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY | | | SEC. R301.2.1 FBC-RESIDENTIAL. | | | | | | PREVIOUS COMMENT: | | | 2-RAS 117 CALCULATIONS SUBMITTED: | | | A)THE BUILDING EXPOSURE IS "C" NOT "B". REVISE AS | | | REQUIRED AND REVISE THE DESIGN PRESSURES ACCORDINGLY. | | | SEC. R301.2.1.4 FBC-RESIDENTIAL. SEC. R301.2.1.2 | | | FBC-RESIDENTIAL. | | | | | | RESPONSE: | | | ENGINEER TO CLARIFY WHY THE DESIGN PRESSURES SHOWN ON | | | THE REVISED RAS 117 CALCULATIONS ARE LOWER FOR BUILDING | | | EXPOSURE "C" THAN THE DESIGN PRESSURES GIVEN FOR | | | EXPOSURE "B". DESIGN PRESSURES CAN NOT BE LOWER. | | | PROVIDE CALCULATIONS. | | | SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY | | | AMENDENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|