| 2023-06-05 13:01:53 | RESIDENTIAL(R3) SECOND REROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23051185 |
| | 1827 PINEHURST DR |
| | |
| | 2- FLAT ROOF NOA 18-0919.12 SUBMITTED: SELECTED |
| | ASSEMBLY SYSTEM TYPE E(4) ON PAGE 57 OF 67 DOESN'T MEET |
| | THE DESIGN PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED |
| | AND SEALED RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL |
| | LIMITATION #7 ON LAST PAGE OF NOA. NEED THE |
| | CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY |
| | SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | RAS 117 CALCULATIONS SUBMITTED: |
| | A)THE BUILDING EXPOSURE IS "C" NOT "B". REVISE AS |
| | REQUIRED AND REVISE THE DESIGN PRESSURES ACCORDINGLY. |
| | SEC. R301.2.1.4 FBC-RESIDENTIAL. SEC. R301.2.1.2 |
| | FBC-RESIDENTIAL. |
| | |
| | B)BASED ON CALCULATED DESIGN PRESSURES, THE SELECTED |
| | ASSEMBLY CAN NOT BE USED BECAUSE ACCORDING TO SEC. 8.1 |
| | OF RAS 117, THE DESIGN PRESSURES OF THE PRODUCT |
| | APPROVAL SHOULD BE APPLICABLE TO ZONE 1' OR 1. REVISE |
| | AS REQUIRED. |
| | |
| | C)ENGINEER OF RECORD TO PROVIDE SKETCH SHOWING THE |
| | DIMENSIONS FOR ALL THE ROOF ZONES APPLICABLE TO THIS |
| | PROJECT AS REQUIRED BY NEW ROOF ZONES ON FIGURE |
| | R301.2(7) FBC-RESIDENTIAL. |
| | |
| | 3- ENGINEER'S SIGNATURE REVIEW: |
| | A) ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| | REQUIREMENTS OF FBPE. THE TEXT BOX LANGUAGE MUST BE |
| | IDENTICAL TO THE SAMPLES PUBLISHED BY FBPE. SEE FBPE.OR |
| | G/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCUMENTS/. AND |
| | REVISE AS REQUIRED TO MATCH. |
| | |
| | B) IT IS NOT CLEAR IF THE DOCUMENT IS DIGITALLY SIGNED |
| | OR ELECTRONICALLY SIGNED. CHECK THE TEXT BOX LANGUAGE . |
| | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGIN |
| | EERING-DOCUMENTS/ |
| | |
| | 61G15-23.005 PROCEDURES FOR ELECTRONICALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | |