| 2023-05-25 15:57:30 | RESIDENTIAL (R3) REROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23051185 |
| | 1827 PINEHURST DR |
| | |
| | NOTE: |
| | LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| | SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| | COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| | THE FLORIDA BUILDING CODE. |
| | |
| | 1- SHINGLES ROOFING UNDERLAYMENT |
| | PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH THE |
| | NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. |
| | SEC. R905.1.1.1 FBC-RESIDENTIAL. |
| | NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 |
| | FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE |
| | PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001 |
| | |
| | 2- FLAT ROOF NOA 18-0919.12 SUBMITTED: SELECTED |
| | ASSEMBLY SYSTEM TYPE E(4) ON PAGE 57 OF 67 DOESN'T MEET |
| | THE DESIGN PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED |
| | AND SEALED RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL |
| | LIMITATION #7 ON LAST PAGE OF NOA. NEED THE |
| | CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY |
| | SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | 3- CONTRACTOR REROOFING AFFIDAVIT IS NOT ACCEPTABLE AT |
| | PLAN REVIEW. THIS IS SUPPOSED TO BE DONE AFTER THE WORK |
| | IS DONE. COORDINATE WITH CHIEF BUILDING INSPECTOR |
| | BEFORE DOING THE JOB FOR AFFIDAVIT REQUIREMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |