Plan Review Notes
Plan Review Notes For Permit 23051151
Permit Number 23051151
Review Stop E
Sequence Number 1
Notes
Date Text
2023-06-30 10:15:09FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE COMPLETE ELECTRICAL SCOPE OF WORK. FBC
 107.2.1, 107.3.5, AND FS 471.003(2), 471.025
  
 2. GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL SHALL BE PROVIDED AS REQUIRED. NEC 210.8(A)
 THROUGH (E).
  
 3. ARC-FAULT CIRCUIT -INTERRUPTER PROTECTION FOR
 DWELLING UNITS.
 ALL 120 VOLTS, SINGLE-PHASE, 15- AND 20-AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS OR DEVICES INSTALLED IN
 DWELLING UNIT KITCHENS, FAMILY ROOMS, DINNING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS, OR SIMILAR ROOMS OR AREAS
 SHALL BE PROTECTED BY ANY OF THE MEANS DESCRIBED IN NEC
 210.12(A)(1) THROUGH (6).
  
 4. PANEL SCHEDULE IN ACCORDANCE WITH NEC 408.4(A).
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  