Plan Review Notes
Plan Review Notes For Permit 23051117
Permit Number 23051117
Review Stop NFIP
Sequence Number 2
Notes
Date Text
2023-07-08 10:14:312ND NFIP REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
 FEMA DESK REFERENCE P 758
 FBC R322 FLOOD-RESISTANT CONSTRUCTION
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CONSTRUCTION DRAWING ELEVATION CERTIFICATE - FOUNDATION
 ONLY
  
 NOTICE: THIS PROJECT IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA (SFHA). THE FLOOD ZONE DESIGNATIONS FOR
 THIS SITE ARE AE 6 WITH A BASE FLOOD ELEVATION (BFE) OF
 6'0" NAVD AND AE 7 WITH A BASE FLOOD ELEVATION OF 7'0"
 NAVD.
 THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO.
 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF FREEBOARD.
 THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE
 9'0" NAVD.
  
 CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729 -
 SECTION 4: THE CODE OF ORDINANCES IS HEREBY AMENDED AT
 CHAPTER 18, BUILDINGS AND BUILDING REGULATIONS, ARTICLE
 II, BUILDING CODE, TO ADD SECTION 18-33, TECHNICAL
 AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL, WHICH
 SHALL READ AS FOLLOWS:
 SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 R322.2.1 ELEVATION REQUIREMENTS.
 BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT
 DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST
 FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION
 PLUS ONE FOOT, OR THE DESIGN FLOOD ELEVATION, WHICHEVER
 IS HIGHER. (PLUS TWO FEET PER CITY ORDINANCE 4729-17).
  
 1. LINE B9 SHOULD BE 6 FEET & 7 FEET.
  
 2. LINE A5 - LAT & LONG. EC INSTRUCTIONS STATES LAT &
 LONG SHALL BE AT THE CENTER OF THE FRONT BUILDING AND
 MUST BE ACCURATE TO WITHIN 66 FEET. PALM BEACH COUNTY
 GIS SHOWS THE LAT & LONG AT 26.74025 AND -80.04935.
 PLEASE REVIEW AND MAKE CORRECTIONS IF NECESSARY.
  
 3. LINE C2E) SHOULD BE 9.0'
  
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  