Plan Review Notes
Plan Review Notes For Permit 23051114
Permit Number 23051114
Review Stop E
Sequence Number 1
Notes
Date Text
2023-06-05 15:13:12FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR PANEL.
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30 445 FBC 107.2.1
  
 SHOW SIZE OF GENERATOR 16,22,24????
  
 SHOW LOAD CALCULATION FOR LOADS ON GENERATOR.
  
 SIGN AND DATE PLAN FOR SUBMITTAL.