| Plan Review Notes For Permit 23051114 |
| Permit Number |
23051114 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-06-05 15:13:12 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE | | | EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND | | | BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR PANEL. | | | SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING | | | TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, | | | 408.30 445 FBC 107.2.1 | | | | | | SHOW SIZE OF GENERATOR 16,22,24???? | | | | | | SHOW LOAD CALCULATION FOR LOADS ON GENERATOR. | | | | | | SIGN AND DATE PLAN FOR SUBMITTAL. |
|