| 2023-06-27 15:52:54 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | 1) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD | | | ANCHORING DETAILS. IF A PREFABRICATED GENERATOR PAD | | | WILL BE USED, SUBMIT SIGNED AND SEALED SITE SPECIFIC | | | ENGINEERING FOR IT. FBC AMENDMENTS 107.2.1 | | | | | | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. FBC-R303.5.1 | | | INTAKE OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR | | | INTAKE OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET | | | (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, | | | SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, | | | ALLEYS, PARKING LOTS AND LOADING DOCKS. SUBMIT A SITE | | | PLAN OR SURVEY SHOWING THE LOCATION OF THE GENERATOR | | | AND NOTE ON THE DRAWING THAT THE GENERATOR EXHAUST IS | | | REQUIRED TO BE 10 FEET FROM OPENINGS INTO THE BUILDING. | | | | | | | | | |
|