| 2023-06-21 07:11:29 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMEND - 105.1/107.3 --THE GREASE TRAP |
| | REQUIRES A SEPARATE PERMIT THAT IS REQUIRED TO BE |
| | APPLIED FOR PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. |
| | YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) |
| | IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A |
| | COMPLETED PERMIT APPLICATION TO |
| | [email protected]. AFTER YOU HAVE THE PERMIT |
| | GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE |
| | LETTER AND I WILL COMPLY THIS COMMENT. |
| | |
| | 2. 2020 FPC 403.1 - PLEASE SHOW THE FIXTURE CALCULATION |
| | TABLE AND THE REQUIRED NUMBER OF FIXTURES FOR THE |
| | OCCUPANT LOAD. |
| | |
| | 3. 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE |
| | FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE |
| | WASTE. ON PAGE 3.0P THE HANDSINK (B3) APPEARS TO BE |
| | DISCHARGING INTO THE GREASE WASTE AND ON THE ISO, IT |
| | APPEARS TO BE GOING INTO THE SANITARY. CAN YOU PLEASE |
| | CLARIFY THE DRAWING ON 3.0P. ALL HAND SINKS SHALL |
| | DISCHARGE INTO THE SANITARY |
| | |
| | 4. 2017 WPB AMENDS 107.2.1 - ON YOUR ISOMETRIC, PAGE |
| | 3.1P, IT APPEARS THAT THE GREASE WASTE EXTENDING TO THE |
| | BAR AREA UP FRONT HAS MISLABLED WHAT IS DISCHARGING |
| | INTO IT. IT SAYS "ICE" BUT APPEARS THAT IT SHOULD BE |
| | THE "GLASSWASHER"? |
| | |
| | 5. 2020 FPC 901.2.1 - PAGE 3.1P - IT APPEARS THAT THE 3 |
| | WATER CLOSETS IN THE WOMEN'S ARE NOT VENTED TO CODE. IF |
| | A CIRCUIT VENT WAS INTENDED, THEN THE VENT SHOULD HAVE |
| | BEEN A DRY VENT BETWEEN THE TWO MOST UPSTREAM FIXTURES. |
| | AN INDIVIDUAL VENT FOR THE MOST UPSTREAM FIXTURE CANNOT |
| | BE THE VENT FOR THE CIRCUIT VENT. IF A WET VENT WAS |
| | INTENDED, ONLY 2 FIXTURES OF EACH TYPE ARE ALLOWED ON A |
| | WET VENT (FPC 912.1). |
| | |
| | 6. 2020 FPC 607.1.1/613.1 - PLEASE INCLUDE A WATER |
| | HEATER DETAIL THAT SHOWS THE CORRECT INSTALLATION OF |
| | THE ASSE 1017 DEVICE AT THE WATER HEATERS. MAKE SURE |
| | THE RETURN LINE IS CORRECTLY ROUTED IN ACCORDANCE WITH |
| | 2020 FPC 607.2.2. THE RETURN MUST BE ROUTED TO THE COLD |
| | WATER INLET PIPE OF THE WATER HEATERS AND THE COLD |
| | WATER INLET PIPE OR THE HOT WATER RETURN CONNECTION OF |
| | THE THERMOSTATIC MIXING VALVE. SHOW A WATER HEATER |
| | DETAIL. |
| | |
| | 7. 2020 FPC 607.1.2/419.5 - PLEASE INCLUDE A PUBLIC |
| | LAVATORY DETAIL THAT INCLUDES THE LIMITING DEVICE |
| | REQUIRED THAT MEETS THE ASSE 1070 STANDARD. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |