Plan Review Notes
Plan Review Notes For Permit 23051110
Permit Number 23051110
Review Stop P
Sequence Number 1
Notes
Date Text
2023-06-21 07:11:291ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND - 105.1/107.3 --THE GREASE TRAP
 REQUIRES A SEPARATE PERMIT THAT IS REQUIRED TO BE
 APPLIED FOR PRIOR TO ISSUANCE OF THE PRIMARY PERMIT.
 YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED)
 IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO
 [email protected]. AFTER YOU HAVE THE PERMIT
 GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE
 LETTER AND I WILL COMPLY THIS COMMENT.
  
 2. 2020 FPC 403.1 - PLEASE SHOW THE FIXTURE CALCULATION
 TABLE AND THE REQUIRED NUMBER OF FIXTURES FOR THE
 OCCUPANT LOAD.
  
 3. 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE
 FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE
 WASTE. ON PAGE 3.0P THE HANDSINK (B3) APPEARS TO BE
 DISCHARGING INTO THE GREASE WASTE AND ON THE ISO, IT
 APPEARS TO BE GOING INTO THE SANITARY. CAN YOU PLEASE
 CLARIFY THE DRAWING ON 3.0P. ALL HAND SINKS SHALL
 DISCHARGE INTO THE SANITARY
  
 4. 2017 WPB AMENDS 107.2.1 - ON YOUR ISOMETRIC, PAGE
 3.1P, IT APPEARS THAT THE GREASE WASTE EXTENDING TO THE
 BAR AREA UP FRONT HAS MISLABLED WHAT IS DISCHARGING
 INTO IT. IT SAYS "ICE" BUT APPEARS THAT IT SHOULD BE
 THE "GLASSWASHER"?
  
 5. 2020 FPC 901.2.1 - PAGE 3.1P - IT APPEARS THAT THE 3
 WATER CLOSETS IN THE WOMEN'S ARE NOT VENTED TO CODE. IF
 A CIRCUIT VENT WAS INTENDED, THEN THE VENT SHOULD HAVE
 BEEN A DRY VENT BETWEEN THE TWO MOST UPSTREAM FIXTURES.
 AN INDIVIDUAL VENT FOR THE MOST UPSTREAM FIXTURE CANNOT
 BE THE VENT FOR THE CIRCUIT VENT. IF A WET VENT WAS
 INTENDED, ONLY 2 FIXTURES OF EACH TYPE ARE ALLOWED ON A
 WET VENT (FPC 912.1).
  
 6. 2020 FPC 607.1.1/613.1 - PLEASE INCLUDE A WATER
 HEATER DETAIL THAT SHOWS THE CORRECT INSTALLATION OF
 THE ASSE 1017 DEVICE AT THE WATER HEATERS. MAKE SURE
 THE RETURN LINE IS CORRECTLY ROUTED IN ACCORDANCE WITH
 2020 FPC 607.2.2. THE RETURN MUST BE ROUTED TO THE COLD
 WATER INLET PIPE OF THE WATER HEATERS AND THE COLD
 WATER INLET PIPE OR THE HOT WATER RETURN CONNECTION OF
 THE THERMOSTATIC MIXING VALVE. SHOW A WATER HEATER
 DETAIL.
  
 7. 2020 FPC 607.1.2/419.5 - PLEASE INCLUDE A PUBLIC
 LAVATORY DETAIL THAT INCLUDES THE LIMITING DEVICE
 REQUIRED THAT MEETS THE ASSE 1070 STANDARD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  