| 2023-05-24 15:44:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 0.11 & E 4.0 - THERE IS AN INDICATION ON THE |
| | LIFE SAFETY SHEET AT DOOR 109 OF "PROVIDE NOT AN EXIT |
| | SIGN, HOWEVER, ON THE ELECTICAL SHEET THERE IS AN |
| | INDICATION OF AN EXIT SIGN. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 2) SHEET A 0.11, A2.02 & A2.01 - THERE ARE NO |
| | INDICATIONS OF A DOOR SCHEDULE ON THESE SHEETS NOR ANY |
| | OTHER. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | PLEASE PROVIDE A DOOR SCHEDULE INDICATING COMPLIANCE |
| | WITH APPLICABLE NFPA 101 OCCUPANCY CHAPTERS INCLUDING |
| | CH 7, MEANS OF EGRESS TO INCLUDE HARDWARE, LOCKS & |
| | LATCHES. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |