Plan Review Notes
Plan Review Notes For Permit 23051075
Permit Number 23051075
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-05-24 15:44:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 0.11 & E 4.0 - THERE IS AN INDICATION ON THE
 LIFE SAFETY SHEET AT DOOR 109 OF "PROVIDE NOT AN EXIT
 SIGN, HOWEVER, ON THE ELECTICAL SHEET THERE IS AN
 INDICATION OF AN EXIT SIGN.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET A 0.11, A2.02 & A2.01 - THERE ARE NO
 INDICATIONS OF A DOOR SCHEDULE ON THESE SHEETS NOR ANY
 OTHER.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE PROVIDE A DOOR SCHEDULE INDICATING COMPLIANCE
 WITH APPLICABLE NFPA 101 OCCUPANCY CHAPTERS INCLUDING
 CH 7, MEANS OF EGRESS TO INCLUDE HARDWARE, LOCKS &
 LATCHES.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  