| 2023-06-07 11:02:18 | WEST PALM BEACH DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 23051075 |
| | ADD: 4805 S DIXIE HWY |
| | CONT: SDJ & ASSOCIATES, LLC |
| | TEL: 561-396-5813 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JUNE 07TH/2023 |
| | ACTION: DENIED |
| | |
| | 1) THIS PROPERTY CONTROL NUMBER ONLY HAS ONE SITUS |
| | ADDRESS OF 4805 S DIXIE HWY. SEPARATE TENANT ADDRESSES |
| | WILL BE REQUIRED. SEE ADDRESSING STOP FOR FURTHER |
| | INFORMATION. 2020 FBC-B 501.2 ADDRESS IDENTIFICATION. |
| | NEW AND EXISTING BUILDINGS SHALL BE PROVIDED WITH |
| | APPROVED |
| | ADDRESS IDENTIFICATION. |
| | |
| | 2) SHEET A2.1 SHOWS THE 2 ACCESSIBLE RESTROOMS 103 & |
| | 104 WITH IN SWING DOORS. TOILET ROOM DOORS. 2020 |
| | FBC-ACCESSIBILITY CODE FIGURE 604.8.1.6 SHOWS AN |
| | OUTSWING DOOR. PLEASE REVIEW SECTION 603.2.3. DOORS |
| | SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR |
| | CLEARANCES REQUIRED FOR ANY FIXTURE. DOORS SHALL BE |
| | PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE. |
| | PLEASE SEE EXCEPTION 2. WHERE TOILET ROOMS ARE FOR |
| | INDIVIDUAL USE AND A CLEAR FLOORS SPACE COMPLYING WITH |
| | 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE |
| | DOOR SWING. WHAT IS MISSING IS THE REQUIRED 30X48 INCH |
| | CLEAR FLOOR SPACE BEYOND THE ARC OF THE DOOR. USUALLY |
| | AT A 45% ANGLE TO THE DOOR ENTRANCE. |
| | |
| | 3) SHEET A2.1 NOR A0.03 ADA RESTROOM DETAILS PROVIDE |
| | DETAILS FOR THE DRINKING FOUNTAINS. 2020 |
| | FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO FEWER |
| | THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 |
| | AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. |
| | SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS. CODE. |
| | SPOUT OUTLETS SHALL COMPLY WITH 602.4 SPOUT HEIGHT. 36 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND FOR |
| | WHEELCHAIR BOUND INDIVIDUALS. |
| | |
| | 4) I DIDN???T FIND A ROOM SCHEDULE, RESTROOMS AND |
| | SERVICE SINKS NEED TO SHOW COMPLIANCE WITH: 2020 FBC-B |
| | 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A RESULT |
| | OF THE BUILDING OFFICIAL INTERPRETATION ON 06/2020. IN |
| | BATHROOMS, RESTROOMS & SERVICE SINK AREAS EPOXY PAINT |
| | IS NO LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT |
| | SURFACE. |
| | |
| | 4A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF |
| | SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A |
| | SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT |
| | LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A |
| | TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 4B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS |
| | SHALL COMPLY WITH 1210.2. |
| | |
| | 5A) A0.10 CODE INFORMATION, BUILDING DATA STATES |
| | BUILDING SPRINKLERED. DOES THIS MEAN IS GOING TO BE |
| | SPRINKLERED OR IS GOING TO BE SPRINKLERED? |
| | |
| | 5B) SHEET A0.10 BUILDING DATA STATES THE CONSTRUCTION |
| | TYPE IS TYPE IV OR HEAVY TIMBER CONSTRUCTION, THE FLOOR |
| | PLAN INDICATES EXISTING CMU BLOCK WALLS. SEE 2023 |
| | SECTION602.4 HEAVY TIMBER CONSTRUCTION. |
| | |
| | 6) SHEET A2.2 SHOWS A WAREHOUSE APPROXIMATELY 2,800 |
| | SQUARE FEET. 2020 FBC-BUILDING SECTION 903.2.9(5) GROUP |
| | S-1 OCCUPANCIES USED FOR STORAGE OF UPHOLSTERED |
| | FURNITURE OR MATTRESSES EXCEEDS 2,500 SQ. FT. REQUIRE |
| | AN AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | 7) SHEET A2.01 SHOWS NEW WINDOWS AND EXTERIOR DOORS. |
| | SHEET A3.03 SHOWS DESIGN PRESSURES BUT THEY ARE NOT |
| | STATED IF THEY ARE IN VASD OR VULT. 2020 FBC-B 1603.1.4 |
| | WIND DESIGN CRITERIA. WIND DESIGN DATA IS FOUND ONS-1. |
| | |
| | 8) MISSING PRODUCT APPROVAL. COMPONENTS & CLADDING. |
| | PLEASE SUBMIT THE COMPONENTS AND CLADDING PRODUCT |
| | APPROVALS. 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP VENTILATORS |
| | |
| | 9) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 10) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 11) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 12) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE |
| | OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER???S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 13) SHEET S-1 INDICATES NICHE ENTRANCE, PLEASE LOCATE |
| | ON SHEET A2.03 THE ROOF PLAN WHERE THIS WORK IS TO |
| | OCCUR? 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| | CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO |
| | INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 14) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT |
| | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |