| Plan Review Notes For Permit 23051030 |
| Permit Number |
23051030 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-06-12 10:07:31 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT- 23051030 | | | 6/12/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) IN RESPONSE TO THE 1ST REVIEW COMMENTS CONCERNING | | | WATER SERVICE AND SANITARY FACILITIES THE ARCHITECT IS | | | STATING THE MODULE UNITS ARE "DRY" UNITS THAT THE | | | STUDENTS WILL USE THE FACILITIES IN THE SOUTH BUILDING. | | | IN ORDER TO VERIFY THE REQUIRED NUMBER OF PLUMBING | | | FIXTURES WILL BE PROVIDED PLEASE PROVIDE FIXTURE | | | CALCULATIONS FOR THE COMBINED STUDENT AND STAFF | | | OCCUPANT LOAD OF THE TEMPORARY MODULE UNITS AND THE | | | SOUTH BUILDING- SEC. 108.2 WPB, SEC. 403.3 & TABLE | | | 403.1 FBC P. PROVIDE A SCHEDULE THAT INDICATES THE | | | REQUIRED NUMBER OF FIXTURES AND THE EXISTING NUMBER OF | | | FIXTURES IN THE SOUTH BUILDING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|