| 2023-05-24 11:37:46 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23051029 |
| | 5/24/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) AS-002 SITE PLAN: PROVIDE POTABLE WATER SERVICE LINE |
| | DETAILS FOR THE TEMPORARY MODULAR CLASSROOM UNIT- SECS. |
| | 301.4, 602.1, 602.2, & 605.3 FBC P. SHOW THE TYPE AND |
| | SIZE OF SERVICE LINE, SERVICE LINE RUN, POINT OF |
| | CONNECTION TO THE CITY MAIN, AND THE LOCATIONS OF THE |
| | WATER METER AND BACKFLOW PREVENTER. INDICATE THE TYPE |
| | AND SIZE OF BACKFLOW PREVENTER TO BE INSTALLED- SEC. |
| | 608.3 FBC P AND SEC. E WPB UTILITIES CROSS CONNECTION |
| | MANUAL. PLEASE NOTE A SEPARATE PLUMBING OR CIVIL PLAN |
| | MAY SUBMITTED AS ALTERNATES TO REVISING THE SITE PLAN- |
| | SEC. 107.2.1 WPB. |
| | A) CONCERNING THE BACKFLOW PREVENTER PLEASE NOTE A |
| | PERMIT APPLICATION SHALL BE SUBMITTED FOR THE |
| | INSTALLATION PRIOR TO APPROVAL OF THE PLUMBING PLAN |
| | REVIEW. YOU CAN SUBMIT AN APPLICATION TBD (TO BE |
| | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| | EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected]. YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE |
| | THE REVIEW STATUS TO PASS. |
| | |
| | 2) AS-002 SITE PLAN: PROVIDE A SANITARY DRAINAGE PLAN |
| | FOR THE MODULAR UNIT- SEC 701.2 & 701.3 FBC P. PROVIDE |
| | EITHER A DIRECT PIPE CONNECTION TO THE CITY SEWER LINE |
| | OR AN ONSITE SYSTEM SUCH AS A HOLDING TANK WITH |
| | PUMP-OUT CAPABILITY. |
| | A) SEWER CONNECTION- SHOW THE TYPE AND SIZE OF BUILDING |
| | DRAIN PIPE, THE DRAIN PIPE RUN, POINT OF CONNECTION TO |
| | THE SEWER LINE, AND CLEANOUT LOCATIONS. |
| | B) PUMP TANK- SHOW THE LOCATION OF THE TANK ON THE |
| | PLAN, PROVIDE A PIPING DIAGRAM, AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |